Thermo Scientific NESLAB ThermoFlex 10000 Recirculating Chiller
Shipping
All products ship from our 30,000 sq. ft. Haverhill, MA warehouse
Shipping
All products ship from our 30,000 sq. ft. Haverhill, MA warehouse
The Thermo Scientific NESLAB ThermoFlex 10000 Recirculating Chiller is a high-capacity process cooling system designed for demanding laboratory, analytical, industrial, and research applications. With up to 10,000 W of cooling capacity at 20°C and 60 Hz, a 17.9 L reservoir, approximately ±0.1°C temperature stability, and a high-temperature configuration capable of operation from +5°C to +90°C, the ThermoFlex 10000 provides substantially greater heat-removal capability than typical benchtop laboratory chillers.
Available used and refurbished from American Instrument Exchange, this ThermoFlex 10000 is designed for continuous closed-loop cooling of analytical instruments, process equipment, manufacturing systems, lasers, semiconductor equipment, reactors, and other high-heat-load applications. A 90-day warranty is included.
High-temperature ThermoFlex 10000 configuration
+5°C to +90°C operating temperature range
Up to 10,000 W cooling capacity at 20°C and 60 Hz
Up to 8,500 W cooling capacity at 20°C and 50 Hz
Approximately ±0.1°C temperature stability
Large 17.9 L / 4.75 gal reservoir
R407C refrigeration system
High-capacity external circulation
Microprocessor-based temperature control
Designed for demanding continuous-duty cooling applications
Closed-loop operation can reduce facility-water consumption
Available with multiple pump configurations
Air-cooled design for this AIE unit
Serviceable air and fluid filtration
Used, refurbished, and tested by American Instrument Exchange
90-day warranty included
The Thermo Scientific NESLAB ThermoFlex 10000 is one of the highest-capacity systems in the ThermoFlex family of recirculating chillers. Designed for applications that generate substantial and continuous heat loads, it provides up to approximately 10 kW of refrigeration capacity under specified 60 Hz operating conditions.
This level of performance separates the ThermoFlex 10000 from smaller laboratory chillers. While a compact chiller may provide several hundred watts or a few kilowatts of heat removal, the ThermoFlex 10000 is intended for substantially more demanding analytical, research, and process equipment.
The integrated 17.9 L reservoir supplies a closed-loop circulation system that continuously removes heat from externally connected equipment and returns the cooled fluid to the process.
Thermo designed the ThermoFlex platform with serviceability in mind. Accessible filtration, straightforward controls, and multiple available pump configurations allow ThermoFlex systems to be matched to a broad range of laboratory and industrial cooling requirements.
| Specification | Details |
|---|---|
| Manufacturer | Thermo Scientific / NESLAB |
| Model | ThermoFlex 10000 |
| Equipment Type | High-capacity recirculating chiller |
| Configuration | High-temperature |
| Temperature Range | +5°C to +90°C |
| Temperature Stability | ±0.1°C |
| Cooling Capacity at 20°C, 60 Hz | Up to 10,000 W / 34,100 BTU/hr |
| Cooling Capacity at 20°C, 50 Hz | Up to 8,500 W / 28,985 BTU/hr |
| Reservoir Capacity | 17.9 L / 4.75 gal |
| Refrigerant | R407C |
| Pump Configuration | Verify installed pump option |
| Condenser Type | Air-cooled |
| Ambient Operating Range | +10°C to +40°C |
| Exterior Dimensions | Approx. 25.2 in. W × 33.8 in. D × 52.3 in. H |
| Electrical Requirements | Verify from unit nameplate prior to purchase |
| Warranty | 90 days |
The ThermoFlex 10000 is designed for applications requiring substantially more cooling capacity than a conventional laboratory recirculating chiller. Typical uses include high-power analytical instrumentation, lasers, semiconductor processing equipment, industrial test systems, reaction and process equipment, heat exchangers, medical equipment, manufacturing systems, and other high-heat-load applications.
In research environments, a ThermoFlex 10000 may provide dedicated cooling for large analytical systems or experimental equipment that generates several kilowatts of continuous heat.
The system can also provide an alternative to once-through facility-water cooling in compatible applications. Instead of continuously drawing water and discharging it to drain, the ThermoFlex circulates a controlled volume of heat-transfer fluid through a closed loop.
This can reduce water consumption while providing greater control over coolant temperature and circulation conditions.
The Thermo Scientific ThermoFlex 10000 is well suited for pharmaceutical and biotechnology facilities, analytical laboratories, semiconductor and electronics research facilities, aerospace laboratories, chemical research groups, industrial R&D facilities, medical-device operations, university research centers, manufacturing environments, and other facilities operating high-heat-load equipment.
Its 10 kW maximum cooling capacity makes it especially relevant when smaller laboratory chillers do not provide sufficient heat removal.
Because the ThermoFlex 10000 is a relatively large floor-standing system, laboratories should consider installation space, ventilation, electrical service, heat rejection, plumbing, and access for routine maintenance before installation.
This ThermoFlex 10000 is configured for operation from approximately +5°C to +90°C with temperature stability of approximately ±0.1°C.
ThermoFlex 10000 systems were available in different temperature configurations. Standard units operate over a narrower range, while high-temperature configurations such as this unit extend the upper setpoint to approximately 90°C.
The refrigeration system provides up to approximately 10,000 W of cooling capacity at a 20°C process temperature when operated at 60 Hz. Maximum rated capacity at 50 Hz is approximately 8,500 W.
Available cooling capacity changes with process temperature, ambient conditions, fluid selection, operating voltage, pump configuration, and hydraulic load.
Applications requiring operation below approximately 10°C also require an appropriate glycol/water heat-transfer mixture to prevent freezing or glazing within the plate heat exchanger.
ThermoFlex 10000 chillers were offered with several different circulation pump configurations to accommodate different combinations of flow and pressure.
This is an important distinction when evaluating a used ThermoFlex 10000. Two units with identical refrigeration capacity and temperature specifications may have substantially different circulation performance depending on the installed pump.
Higher-flow configurations can support equipment requiring substantial coolant movement, while higher-pressure pump options are better suited for more restrictive external cooling circuits.
For this reason, American Instrument Exchange recommends verifying the installed pump configuration when the application has a defined minimum flow rate or pressure requirement.
Actual delivered flow also depends on tubing diameter and length, fittings, fluid viscosity, process temperature, elevation, and hydraulic resistance within the connected equipment.
This used Thermo Scientific NESLAB ThermoFlex 10000 Recirculating Chiller is refurbished and tested by American Instrument Exchange before shipment. Our technicians inspect the refrigeration system, compressor, circulation pump, temperature controller, display, reservoir, condenser, filtration components, electrical systems, safety controls, and external fluid connections.
Temperature-controlled equipment is tested using NIST-traceable probes and data loggers. The refrigeration system is operated for extended periods to evaluate cooling performance, circulation, temperature regulation, controller operation, and overall system stability.
The reservoir and accessible fluid-contact areas are cleaned and inspected before shipment. Air and fluid filtration components are also inspected as part of the refurbishment process.
Because the ThermoFlex 10000 can be configured for demanding process applications, customers are encouraged to provide their intended coolant temperature, estimated thermal load, required flow and pressure, and other operating requirements before shipment.
When practical, American Instrument Exchange can incorporate customer-requested conditions into final testing.
A 90-day warranty is included with this refurbished Thermo Scientific chiller.
The ThermoFlex 10000 is primarily intended for applications requiring substantial heat removal. Its maximum 10 kW refrigeration capacity makes it significantly more powerful than typical benchtop laboratory chillers.
Cooling capacity should nevertheless be evaluated at the actual intended operating temperature. A chiller's maximum wattage rating alone does not establish whether it can maintain a particular process temperature under a continuous thermal load.
Pump configuration is equally important with the ThermoFlex platform. Buyers should determine the required flow and pressure of the connected equipment and compare those requirements with the pump installed in the specific chiller.
The high-temperature configuration also distinguishes this unit from standard ThermoFlex 10000 systems. Its +5°C to +90°C operating range provides considerably greater temperature flexibility for applications that require controlled fluid temperatures above the standard range.
Finally, laboratories should verify available electrical service before purchase. ThermoFlex 10000 systems were manufactured in multiple electrical configurations, and the requirements of the individual unit should be confirmed from its nameplate.
American Instrument Exchange can help compare available recirculating chillers based on thermal load, coolant temperature, pump requirements, electrical service, and application.
American Instrument Exchange stocks a range of laboratory circulators, including high-capacity process chillers, compact recirculating chillers, refrigerated/heated circulators, and heated circulating baths. Laboratories using the ThermoFlex 10000 may also require reactors and fermenters, evaporators and extractors, laboratory water baths, or other refurbished laboratory equipment.
The ThermoFlex 10000 provides up to approximately 10,000 W, or 10 kW, of cooling capacity at a 20°C process temperature when operated at 60 Hz. Maximum rated capacity at 50 Hz is approximately 8,500 W.
This unit is the high-temperature configuration and operates from approximately +5°C to +90°C. Standard ThermoFlex 10000 configurations may have a narrower temperature range.
Thermo specifies temperature stability of approximately ±0.1°C under appropriate operating conditions.
The ThermoFlex 10000 has a 17.9 L, or approximately 4.75 gallon, reservoir.
Thermo offered the ThermoFlex 10000 with multiple pump options providing different combinations of flow and pressure. The installed pump configuration should be verified for applications with specific circulation requirements.
In many compatible applications, yes. Its closed-loop refrigeration system can reduce or eliminate continuous consumption of facility water while providing controlled coolant temperature and circulation.
Thermo specifies an appropriate glycol/water mixture for operation below approximately 10°C to prevent freezing or glazing within the plate heat exchanger. Fluid selection should follow manufacturer recommendations for the intended operating temperature.
No. The ThermoFlex 10000 is a large floor-standing process chiller measuring approximately 25.2 inches wide, 33.8 inches deep, and 52.3 inches high in its air-cooled configuration.
Yes. This used Thermo Scientific NESLAB ThermoFlex 10000 is refurbished and tested by American Instrument Exchange and includes a 90-day warranty.
CLICK HERE to see the Thermo Neslab ThermoFlex 10000 on our YouTube channel
Yes, all equipment from American Instrument Exchange comes with a warranty.
Used/reconditioned/refurbished equipment is tested to make sure it operates to the manufacturer's specifications and comes with a 90-day warranty (unless otherwise noted). New equipment comes with a warranty from the manufacturer.
Testing requirements vary across all the equipment categories we sell. Temperature controlled units are tested with NIST traceable probes and data loggers. Gaskets, external housing, glass, handles, controls and control screens are all thoroughly inspected for integrity and functionality.
We test all equipment using the manufacturer's parameters and specifications to confirm that the unit operates properly.
We can ship products both nationally and internationally using a well-established network of transporters. Smaller items will ship via UPS. Larger equipment will be palletized and shipped either LTL or air-ride, depending on the specific equipment and/or delivery requirements.
American Instrument Exchange will accept the return of any product that is not working as represented and could not be replaced or repaired to the customer's satisfaction during the warranty period. Customers who cancel orders after refurbishing has begun will be subject to a cancellation and restocking fee of between 20% and 40%.
Yes – call or email us today with a list of equipment you're looking for and we can potentially put together a quote that includes a discount.
We strive to keep our pricing competitive and reasonable. If you find comparable items for sale at a lower price from other vendors please send us a link and or quote for the item and we'll do our best to match or beat the price.
Customers are welcome to make an appointment to view equipment in our warehouse. Given our workload we may not be able to test or clean the equipment prior to your arrival if you have not committed to an order.
1023 Western Avenue is a working warehouse, not a showroom, and customers should dress appropriately and wear closed toe shoes.
Yes – please see our repair services page for more information.